Bomba Requirements for a Factory or Warehouse in Rawang, Serendah and Shah Alam: Sprinklers, Hose Reels, Hydrants, Alarms and Who Pays
In Selangor, required fire systems follow floor area and use (Tenth Schedule, Selangor Uniform Building By-Laws, amended 2012). A single-storey factory under 750 m² has none listed; 750 to 1,000 m² needs a 25 kg trolley extinguisher and manual alarm; above 1,000 m², a hose reel and detectors; above 2,000 m², sprinklers too. The lease decides who pays.
Key Takeaways
- Selangor sets the list by floor area and use. The Tenth Schedule of the Selangor Uniform Building By-Laws 1986, as replaced by Sel. P.U. 142/2012, decides which fire systems a factory or warehouse in Rawang, Serendah or Shah Alam must have.
- Small terrace units sit below the first line. A single-storey factory under 750 m² (about 8,073 sq ft) has no fixed system listed. From 750 m² it needs a 25 kg trolley extinguisher and a manual fire alarm, from 1,001 m² a hose reel and automatic detectors, and above 2,000 m² (about 21,528 sq ft) sprinklers as well.
- Warehouses of combustible goods reach sprinklers sooner. A single-storey store of burnable goods needs sprinklers once it passes 1,000 m² or 7,000 m³, so a high roof can pull a smaller floor into the sprinkler row.
- Hydrants follow distance, not floor area. Every building must be served by at least one hydrant within 45 metres of the fire brigade access, with hydrants no more than 90 metres apart.
- The law does not split the bill, the lease does. Bomba serves a fire-hazard notice on the occupier who caused the hazard, or else on the owner, so the tenancy agreement should say who services, who upgrades and who pays.
Which rules decide the fire systems in a factory in Rawang, Serendah or Shah Alam?
Building rules in Malaysia are made state by state under the Street, Drainage and Building Act 1974, so for all three of my areas the text that counts is the Selangor Uniform Building By-Laws 1986. Its by-law 225(1) says every building shall be provided with means of detecting, warning and extinguishing fire as specified in the Tenth Schedule (Selangor by-laws, consolidated to Sel. P.U. 142/2012). The Tenth Schedule itself was replaced in December 2012 by Sel. P.U. 142/2012, and the Local Government Department's list of state gazettes shows that 2012 amendment as the latest one for Selangor (JKT list of state by-laws).
Why say this so carefully? Many summaries online quote the national model with its 2021 amendment. The Local Government Department's own consolidated copy of that model says plainly that it is only a model by-law and that only each state's by-laws carry enforcement power (UBBL 1984 incorporating the 2021 amendment). The two tables differ on details a buyer cares about. For a single-storey factory of 750 to 1,000 m², the national model lists a hose reel, while the Selangor table lists a 25 kg trolley extinguisher. Older buildings also carry the systems that were required when their plans were approved, so I compare what is installed with the current Selangor table, then ask what the client's use would change.
The by-laws also name the Malaysian Standard each system must meet: MS 1489 for hose reels and hydrants, MS 1910 for sprinklers and MS 1539 for portable extinguishers (by-laws 225, 226A, 227 and 228). Above the table, Bomba can ask for more: extra hydrants depending on the size, location and fire engine access of the building (by-law 225(3)), and fixed protection for special hazards (by-law 236).
What does a factory need at each floor area?
These are the factory rows of the Selangor Tenth Schedule (Sel. P.U. 142/2012). Floor area means the area on the approved building plan.
| Factory | Floor area | Extinguishing system | Detection and alarm |
|---|---|---|---|
| Single storey, detached or terrace | Under 750 m² (about 8,073 sq ft) | None listed | None listed |
| Single storey, detached or terrace | 750 to 1,000 m² | 25 kg trolley extinguisher | Manual electric fire alarm |
| Single storey, detached or terrace | 1,001 to 2,000 m² | Hose reel | Manual alarm and automatic fire detectors |
| Single storey, detached or terrace | Over 2,000 m² (about 21,528 sq ft) | Hose reel and sprinklers | Manual alarm, centralised monitoring, fire command centre |
| Two storeys, each floor a separate compartment | Under 500 m² per floor | 25 kg trolley extinguisher | Manual electric fire alarm |
| Two storeys, each floor a separate compartment | 500 to 1,000 m² per floor | Hose reel | Manual alarm and automatic fire detectors |
| Two storeys, each floor a separate compartment | Over 1,000 m² per floor | Hose reel and sprinklers | Manual alarm, centralised monitoring, fire command centre |
| Vehicle assembly and similar plants | 2,001 to 5,000 m² | Hose reel and pressurised hydrant | Manual electric fire alarm |
| Vehicle assembly and similar plants | Over 5,000 m² | Hose reel, sprinklers and pressurised hydrant | Manual alarm, automatic detectors, centralised monitoring, fire command centre |
Two notes under the factory rows carry weight. A factory that operates after dark must provide emergency lighting as the Director General of Fire and Rescue requires, and special risks, hazardous processes or hazardous storage must have whatever protection he requires. A building with a hazardous process has its own row, which can call for hose reels, sprinklers, gas systems or pressurised hydrants and the full range of alarms. Note 1 of the schedule lists the hazardous areas, among them boiler rooms, transformer and switch rooms, indoor storage of flammable liquids, and process equipment, pump rooms, open tanks, dip tanks and mixing tanks.
To put these lines next to real units: in the JPPH-registered tenancies of the last 24 months, the median terrace factory let in Rawang and Kundang covered about 2,400 sq ft, in Serendah about 2,000 sq ft and in Shah Alam about 2,600 sq ft, all far below 750 m². In Shah Alam the median semi-detached factory tenancy covered about 8,810 sq ft and the median detached one about 9,170 sq ft, roughly 818 m² and 852 m² (Rawang and Kundang, Serendah, Shah Alam transaction data). A single-storey building of that size lands in the 750 to 1,000 m² row. The row follows the whole building's floor area and storeys on the approved plan, not the area written in the tenancy, so I always read the plan.
What changes for a warehouse?
The storage rows split goods into non-combustible products, such as clay or bleaching earth, and combustible products. Cartons, plastics, textiles, timber pallets and most packed goods burn, so most warehouses in Rawang and Shah Alam fall under the combustible rows (Sel. P.U. 142/2012):
| Warehouse of combustible goods | Floor area or volume | Extinguishing system | Detection and alarm |
|---|---|---|---|
| Single storey | Under 250 m² | None listed | None listed |
| Single storey | 250 to 500 m² | Portable extinguishers | Manual electric fire alarm |
| Single storey | 501 to 1,000 m² and under 7,000 m³ | Hose reel | Manual alarm and automatic fire detectors |
| Single storey | Over 1,000 m² or over 7,000 m³ | Hose reel and sprinklers | Manual alarm, centralised monitoring, fire command centre |
| Single storey, open sided | Over 1,000 m² | Hose reel | Manual electric fire alarm |
| Two storeys and over | Under 1,000 m² and under 7,000 m³ | Hose reel | None listed |
| Two storeys and over | Over 1,000 m² or over 7,000 m³ | Hose reel and sprinklers | Manual alarm, centralised monitoring, fire command centre |
A store of non-combustible products needs nothing listed while it is single storey and under 2,000 m²; at two storeys or over 2,000 m² it needs a hose reel and a manual fire alarm.
The volume test is the one people miss. A single-storey store of 900 m² with an average internal height of 8 metres holds 7,200 m³, over the 7,000 m³ line even though the floor is under 1,000 m². For a warehouse I therefore ask for the section drawing as well as the floor plan.
The second trap is a change of use. A single-storey unit of 900 m² approved and fitted as a factory needs a trolley extinguisher and a manual alarm. The same floor filled with cartons as a store needs a hose reel and detectors, and sprinklers once the volume passes 7,000 m³. When a client plans to store more than they make, I read the storage rows first. Ms Teh's light, medium and heavy industry guide helps when the activity itself is in question.
Where do hydrants, emergency lights and the fire certificate come in?
Hydrants. By-law 225(2), as amended in 2012, says every building shall be served by at least one fire hydrant not more than 45 metres from the fire brigade access, designed and installed to MS 1489, and that hydrants shall be located not more than 90 metres apart (Selangor by-laws). On a viewing I find the nearest hydrant pillar and pace it from the point where a fire engine would stop. The national 2021 model measures it differently, 30 metres from an entry to the building or a breeching inlet, one more reason to read the Selangor text.
Emergency lights. By-law 253A requires emergency lighting good enough for escape, either self-contained units to MS 619 or fittings fed by an emergency power system or a central battery bank, lasting at least one hour when the normal supply fails.
Plans and sign-off. Fire installations do not go in on a contractor's word. By-law 245 requires the plans, drawings and calculations of all fire fighting installations to be submitted to the Fire Authority before work starts, and anything that departs from Parts VII and VIII needs the Director General's approval first. At completion, Form G9, the stage certificate for active fire-fighting works, is signed by the trade contractor and the submitting engineer, with a letter of clearance from the Fire Department attached; Form G8 does the same for passive fire protection.
Fire certificate. Once a factory has 2,000 m² of floor area fitted with automatic sprinklers, or runs a hazardous process, it becomes a designated premises and needs a yearly Bomba fire certificate. That paper is covered in my fire certificate guide, so I will not repeat it here.
Who pays for fire protection in a rented factory or warehouse?
No Act divides the cost between landlord and tenant. What the law does fix is who Bomba comes after. The Fire Services Act 1988 counts as a fire hazard both the absence of fire-fighting equipment required by law and equipment that is not in efficient working order (Act 341, section 2). A fire-hazard abatement notice goes to the person whose act, default or sufferance caused the hazard if that person is the occupier; otherwise, or when that person is not known, it goes to the owner (section 8). For a designated premises, the fire certificate regulations make the owner or the occupier the applicant according to who owns or maintains the fire installation, and the fire safety organization must keep every installation maintained and in good condition (regulations 1B and 6E(f) of the Fire Certificate Regulations).
So the tenancy agreement has to carry the split. When I prepare a tenancy for a factory in Rawang, Serendah or Shah Alam, I ask both sides to settle five points in writing:
- At handover. The landlord delivers the systems that the building's approved size and use require, in working order, with the latest service report and the Form G9 from the CCC file.
- During the term. The lease names who services the extinguishers, hose reels, alarm panel, sprinkler pumps and emergency lights, how often, and who keeps the records. In a single-tenant building the tenant is the one on site when Bomba inspects, so the records should sit there.
- Upgrades the tenant causes. Taller racking, burnable stock in a unit fitted for light assembly, a spray booth or solvent store, office partitions or a mezzanine are at the tenant's cost, after the landlord's written consent and after the plans go to Bomba under by-law 245.
- Defects in what was approved. A system that the approved use and floor area already required but that is missing or broken at handover is the landlord's to put right.
- At the end. The lease says whether the tenant removes its additions or leaves them.
These are the points I raise, not fixed rules; the amounts and wording are for the two parties and their lawyers. My guide on screening a tenant and protecting the landlord in the lease covers the other clauses.
What do I check on a viewing?
- The approved plan. Total floor area, number of storeys, and the section drawing for the internal height.
- The client's use. What will be made or stored, whether it burns, and whether any process could count as hazardous.
- The table row. Which row of the Selangor Tenth Schedule that gives, and whether the installed systems match it.
- Hose reels. The drum, hose and nozzle, and the pump and tank behind them.
- Sprinklers. Heads under the roof, the control valve, pump room and tank, and stock or racking kept clear below the heads.
- The alarm panel. Whether it shows a fault or an isolated zone, and where the break-glass points are.
- Extinguishers. Service tags, and the 25 kg trolley unit where the row calls for one.
- The hydrant. Its distance from the fire brigade access.
- Emergency lights and exit signs. Tested with the power off if the landlord agrees.
- The papers. CCC, Forms G8 and G9 with the Bomba clearance letter, the latest service report, and any notice from Bomba.
What do the councils ask for when you license the premises?
- Rawang, Majlis Perbandaran Selayang (MPS). The licence renewal documents include a copy of the receipt for the fire extinguisher inspection (Bomba). One approval condition is that the premises meet the safety requirements of the Fire Department, and a licensed building may not be altered without permission (MPS licence page).
- Serendah, Bukit Beruntung, Batang Kali and Sungai Choh, Majlis Perbandaran Hulu Selangor (MPHS). The composite licence form asks for the fire extinguisher purchase sticker, not expired and showing the premises address, lists approval from the Fire and Rescue Department among the documents for industrial and manufacturing activity, and asks for the renovation approval receipt where there are partitions or alterations. Its conditions require extinguishers that have not expired and flammable materials kept in closed containers (MPHS form).
- Shah Alam, Majlis Bandaraya Shah Alam (MBSA). The composite licence asks for a copy of the CCC or CF and a floor plan sketch, with a RM100 processing fee for an industrial application (MBSA).
You will find more on each place on the Rawang, Serendah and Shah Alam pages, and current units on the factory and warehouse pages.
To have the fire systems of a factory or warehouse in Rawang, Serendah or Shah Alam checked against the Selangor table before you sign, WhatsApp Jason Low (Probationary Estate Agent PEA 1478, CID Realtors Sdn Bhd E(1) 1855) on +60 12-288 1834.
Questions people ask
01What are the Bomba requirements for a factory in Selangor?+
They are set by floor area and use in the Tenth Schedule of the Selangor Uniform Building By-Laws, as replaced by Sel. P.U. 142/2012. A single-storey factory under 750 m² has no fixed system listed, 750 to 1,000 m² needs a 25 kg trolley extinguisher and a manual fire alarm, 1,001 to 2,000 m² a hose reel with manual alarm and automatic detectors, and above 2,000 m² sprinklers as well. Bomba can require more for hazardous processes or poor fire engine access.
02Is a sprinkler system compulsory for a warehouse in Selangor?+
For a single-storey warehouse of combustible goods, sprinklers come in once the floor area passes 1,000 m² or the volume passes 7,000 m³. For two storeys and over, the same 1,000 m² or 7,000 m³ line applies to the total floor area. A store of non-combustible products such as clay needs only a hose reel and manual alarm once it passes 2,000 m² or two storeys.
03Does a small terrace factory need a hose reel?+
Not under the Selangor table if it is a single-storey unit under 750 m², which covers the median terrace factory tenancies registered in Rawang, Serendah and Shah Alam. The council still expects portable extinguishers: MPHS asks for an unexpired extinguisher purchase sticker and MPS asks for the extinguisher inspection receipt when the licence is renewed.
04How far must a fire hydrant be from a factory in Selangor?+
By-law 225(2) of the Selangor by-laws, as amended in 2012, requires every building to be served by at least one fire hydrant not more than 45 metres from the fire brigade access, designed and installed to MS 1489, with hydrants not more than 90 metres apart. Bomba may require extra hydrants depending on the size, location and fire engine access of the building.
05Who pays for fire protection upgrades in a rented factory?+
No law divides it; the tenancy agreement does. A fair split is that the landlord hands over the systems the approved building already needs in working order, while upgrades caused by the tenant's use, such as taller racking, burnable stock or a hazardous process, are at the tenant's cost after landlord consent and Bomba plan submission. Bomba itself serves notices on the occupier who caused a hazard, or otherwise on the owner.
06Do I need Bomba approval before changing the fire systems in a factory?+
Yes. By-law 245 of the Selangor by-laws requires the plans, drawings and calculations of all fire fighting installations to be submitted to the Fire Authority before work starts, and any installation that departs from Parts VII and VIII needs the Director General's approval first. In a designated premises, a material change also has to be notified to Bomba before work begins.
07How many emergency exits does a factory in Rawang or Shah Alam need under the Selangor by-laws?+
There is no fixed number, because no public list gives an exit count for a factory. The exits are set by the approved building plan and the Selangor Uniform Building By-Laws. What by-law 253A does require is emergency lighting good enough for escape, lasting at least one hour if the normal supply fails. Before you sign, check the approved plan and confirm the exit requirements with MPS, MPHS or MBSA.
08How much does it cost to upgrade a factory's fire protection system in Rawang or Serendah?+
There is no published figure, because the cost depends on which row of the Selangor Tenth Schedule the building falls into and what is already installed. A single-storey factory of 750 to 1,000 m² needs a 25 kg trolley extinguisher and a manual alarm, while one above 2,000 m² needs a hose reel and sprinklers. Ask licensed contractors for quotations, and make sure the plans go to Bomba under by-law 245 before any work starts.
Sources
- Selangor Uniform Building (Amendment) (No. 2) By-Laws 2012, Sel. P.U. 142/2012: new Tenth Schedule (Local Government Department, JKT)
- Undang-Undang Kecil Bangunan Seragam Selangor (Pindaan) 2012, Sel. P.U. 142/2012 (Malay text, JKT)
- Selangor Uniform Building By-Laws 1986, Sel. P.U. 26/1985, consolidated to Sel. P.U. 142/2012: by-laws 225 to 245, 253A and Forms G8, G9 (JKT)
- JKT: UBBL 1984 amendments gazetted by each state authority (Selangor list ends at 2012)
- JKT: Uniform Building By-Laws 1984 incorporating the 2021 amendment (national model, first edition 2022)
- Laws of Malaysia: Fire Services Act 1988 (Act 341), sections 2, 8 and 32 (AGC reprint)
- Laws of Malaysia: Fire Services (Fire Certificate) Regulations 2001, regulations 1B and 6E (reprint as at 1 April 2023)
- Majlis Perbandaran Selayang: licence documents and approval conditions
- Majlis Perbandaran Hulu Selangor: composite business premises licence form
- Majlis Bandaraya Shah Alam: composite licence (business and industrial)
- FactoryHub: JPPH-registered industrial transactions and tenancies, Rawang and Kundang
- FactoryHub: JPPH-registered industrial transactions and tenancies, Serendah
- FactoryHub: JPPH-registered industrial transactions and tenancies, Shah Alam
Units on the market nearby
Semi-D Factory for Rent in Saujana Teknologi Rawang, Rawang, 6,525 sq ft
RM 10,500/month
Semi-Detached Factory for Sale or Rent in Saujana Rawang, Rawang, 8,000 sq ft
RM 4,000,000 · RM 15,000/month
Detached Factory for Rent in Batu 17 Rawang, 9,000 sq ft
RM 21,000/month
More on licences, bomba and approvals
- Business Premise Licence for a Factory or Warehouse in Rawang, Serendah and Shah Alam: What MPS, MPHS and MBSA Ask For, Signboard Rules, Timelines and Refusals
- Light Industrial Factory, or Medium or Heavy? How Zoning Classes and Buffer Zones Work in Rawang, Serendah and Shah Alam, and How I Check a Unit
- Illegal Factory Extension in Rawang, Serendah or Shah Alam: What MPS, MPHS and MBSA Can Do and How to Make It Legal
- Factory Wastewater in Rawang, Serendah and Shah Alam: Industrial Effluent Regulations 2009, LUAS Licences and What I Check in the Building